P046 Detecting and attributing underwater data centres

Can an underwater data centre built for evasion be detected, and told apart from commercial subsea infrastructure (commercial underwater data centres, offshore wind, cables)?

Detecting an underwater data centre built for evasion (heat plume, acoustic and power signatures, cable installations) and telling it apart from commercial subsea infrastructure.

Terms: UDC (underwater data centre): a sealed data centre placed on the seabed and cooled by the surrounding water.

Status

Analyzed A desk analysis (order-of-magnitude physics and logistics) of thermal, acoustic, optical and SAR detection of a 150 to 200 MW, 100,000-H100-equivalent underwater build, finding construction and maintenance the detectable phases; attribution against offshore wind, platforms and ships' generators is unsolved ('detection is not the same as attribution'); no field measurement, no sensor trial.

Thermal detection of an operational pod is unlikely outside shallow, calm water; acoustic detection is marginally more effective, but faces limitations in attribution; and optical/SAR monitoring is most powerful during construction and maintenance
Teague, Rajmohan & Muehlhaeuser (2026), Could Underwater Data Centers Pose a Risk to AI Treaty Verification? (arXiv 2609.18824v1) (2026-09-16), L21–24

Raised in: Baker, Kulp, Marks, Brundage & Heim (2025), Verifying International Agreements on AI: Six Layers of Verification for Rules on Large-Scale AI Development and Deployment (RAND WR-A4077-1); Wasil, Reed, Miller & Barnett (2024), Verification Methods for International AI Agreements; Teague, Rajmohan & Muehlhaeuser (2026), Could Underwater Data Centers Pose a Risk to AI Treaty Verification?, arXiv 2609.18824.

Sub-questions

IDSub-questionWhat the sources report
P046.1Are frontier-scale underwater data centres technically feasible and detectable?partly answered
P046.2With spare redundant links and no hands-on access, what schedule penalty does a 100k-GPU underwater run incur?open
P046.3Can satellite thermal IR detect the water-temperature plume of an N-MW cluster rejecting heat into a lake, river or coast (minimum detectable MW)?a source suggests an answer (not checked)
P046.4Does harmonic structure plus spatial stationarity separate a 150 MW subsea load from offshore wind or platform hum?open
P046.5Which observable (pod count, power-cable rating, maintenance cadence) separates a 150 MW evasion build from the largest commercial UDC?implied by a source, not stated as open

Sub-questions not yet stated precisely enough to check

IDSub-question
P046.6Can optical/SAR satellites distinguish evasion-build cable installations from pre-regime or commercial ones?
P046.7Does scaled modular pressure-vessel production erode the supply-chain chokepoint?

Possibly relevant work found by automated search

Found by AI agents searching for this problem's sub-questions, mostly by keyword and citation in the OpenAlex scholarly database and on the web; a second AI pass reviewed each one, and we spot-checked some by hand. They seemed reasonably related, as far as one can tell from outside each paper's field. Some come from neighbouring fields, such as arms control and financial audit, and bear on the problem by analogy. Not reviewed against the status above; a paper listed here does not change that status. 928 of 1052 quotes checked word for word against the paper's text.

For P046.3: Can satellite thermal IR detect the water-temperature plume of an N-MW cluster rejecting heat into a lake, river or coast (minimum detectable MW)?

Data